6 Communication settings and guide of HMI connecting with controller
Supported Device
EB-MOD2P-01
Device Bit Address Word Address Format Notes
Internal/External Output bit 0X1-60 ------ DDDDD
Internal/External Input bit 1X1-60 ------ DDDDD
Data Register bit 3X_bit1-60 ------ DDDDD
Data Register bit 4X_bit1-60 ------ DDDDD
Simulate Input Register bit ------ 3X1-60 DDDDD
Data Register ------ 4X1-60 DDDDD
Data Register ------ 5X1-60 DDDDD
Data Register ------ 6X1-60 DDDDD
Data Register ------ 3X-DINV 1-60 DDDDD
Data Register ------ 4X-DINV 1-60 DDDDD
Note:The correspondence between the device of Kinco HMIware and the s7-300 software, as follows:
4X-DINV------------PID
e.g.:4X-DINV1------------PID256 4X-DINV3------------PID260
3X-DINV------------PQD
e.g.:3X-DINV1------------PQD256 3X-DINV3------------PQD260
4X -------------------PIW
e.g.:4X1 --------------------PIW256 4X2--------------------PIW258
3X--------------------PQW
e.g.:3X1---------------------PQW256 3X2---------------------PQW258
0X--------------------I
e.g.:0X1--------------------I0.0 0X9--------------------I1.0
1X--------------------Q
e.g.:1X1--------------------Q0.0 1X9--------------------Q1.0
4X_BIT -------------------PIW(binary)
e.g.:4X_BIT1.0~~1.15-------------------PIW256(binary)
3X_BIT--------------------PQW(binary)
e.g. :3X_BIT1.0~~1.15--------------------PQW256(binary)
PLC software setting
Setup the GSD in the S7-300 software
Procedure :
(1).Close all stations in “HW Config”.
(2).And select “option”-->”setup GSD”.
(3). In the “installation *.GSD file” dialog box, select Source: folders contain *. GSD file, or the
STEP 7 project contain *. GSD file
(4).Select one or more files from *.GSD file list, and then click on "install" button.
Copy the icon (. BMP file) to the relevant path, such as BRIDGE product:Bitmap_Device =
"EVIEW", that copy the "EVIEW" BMP file to the relevant path: c:\siemens\step7\s7data\nsbmp or
c:\siemens\cpbv51\bitmaps
- 80 -