6 Communication settings and guide of HMI connecting with controller
Input(X) Relay
X0.0~109.F ------ DDD.H
Output(Y) Relay
Y0.0~109.F ------ DDD.H
Timer(T) Relay
T0~1007 ------ DDDD
Counter(C) Relay
C1008~1023 ------ DDDD
Link Relay(L) L0.0~127.F ------ DDD.H
Internal Relay(R)
R0.0~255.F
R900.0~911.F
------ DDD.H
Timer/Counter set value(SV) ------ EV0~1023 DDDD
Timer/Counter elapse value(EV) ------ SV0~1023 DDDD
Data Register(DT) ------ DT0~32764 DDDDD
Note:
1). Example: X address: 01 in the PLC corresponds to 0.1 in the Kinco HMIware; X address: 1F in the
PLC corresponds to 1.F in the Kinco HMIware.Y\R register address, and so on.
2). EV registers in the range of addresses on the touch screen can be set to 32767, but only supports
the 9999 agreement.
Cable Diagram
FP RS232 communication
HMI terminal
Controller terminal
9pin D-SUB female/male
5 pin Mini Din (male)
3 TX 3 RXD
2 RX 2 TXD
5 GND 1 GND
RS232 communication
Tool port:
CPU port:
- 170 -