6 Communication settings and guide of HMI connecting with controller
Sequence code(Read Only) ------ Array Code 0-3 H
Basic parameter value(Read Only) ------ Basic_Read 00-42 HH
OUT1_W,OUT2_W(Write Only) ------ Out_Write 0-1 H
PV1,PV2(Read Only) ------ PV_Read 0-1 H
Reference(Read & Write) ------ Reference 300-952 HHH
Basic_Read operatable address
PLC addr
(HEX)
Parameter R/W Parameters mean
00H
PV_W Read Measurements
01H
SV_W Read Setting value
02H
OUT1_W Read Output1 value
03H
OUT2_W Read Output2 value
04H
EXE_FLG Read Execute_flag(no execute=0)
05H
EV_FLG Read Event_flag(no event output 0000)
06H
Reserve Read value:0000H
07H
EXE_PID Read Execute_PID No.
09H
HB_W Read Heater break alarm
0AH
HL_W Read Heater loop alarm
0BH
DI_FLG Read DI status flag
10H
UNIT Read Measurement unit
11H
RANGE Read Measuring range
12H
CJ Read Cold junction compensation 0=Internal 1=External
13H
DP Read Decimal position, 0=none 1=0.1 2=0.01 3=0.001 4=0.0001
14H
SC_L Read PV lower limit side scaling
15H
SC_H Read PV higher limit side scaling
16H
DPFLG Read 0=show 1=cancel
20H
E_PRG Read
Execute flag of program
21H
E_PTN Read Execution step No. of step loop
22H
Reserve Read Reserve
23H
E_RPT Read Curve repeat time
24H
E_STP Read Execution count of step loop
25H
E_TIM Read Step time
26H
E_PID Read PID No. execution
29H
E_STPRPT Read Number of steps
42H
POSI Read
Seven switches(feedback 0-100)
Ctrl_Write operatable address example
PLC addr(HEX) Parameter R/W Parameters mean
184H
AT write Execution automatically adjustment 0:OFF1:ON
18CH
COM write Communication Protocol:0: LOC 1: COM
- 259 -